Hydronic fan coil for heating and cooling, with an integrated 3-way valve. AR: external 0-10 V analogue or contact control.
Heating output at 45°C flow / 40°C return and 20°C room air: 0.99 / 1.45 / 2.50 kW at low / medium / high fan speed. Select the emitter at the intended fan speed and system design temperatures.
| Performance | Low fan | Medium fan | High fan |
|---|
| Heating at 45/40°C water,20°C room (kW) | 0.99 | 1.45 | 2.5 |
|---|
| Total cooling at 7/12°C water,27°CDB/19°CWB air (kW) | 0.77 | 1.09 | 1.82 |
|---|
| Sound power LwA (dB) | 43 | 50 | 58 |
|---|
| Sound pressure LpA (dB) | 34 | 41 | 49 |
|---|
| Air flow (m³/h) | 200 | 280 | 430 |
|---|
| Electrical input (W) | 9 | 13 | 27 |
|---|
Dimensions W × H × D: 1306 × 380 × 129 mm closed / 150 mm maximum flap projection. Connections: 3/4 inch Eurocone. Maximum operating pressure: 8 bar. Supply: 230 V, single phase, 50 Hz.
Sound pressure is the manufacturer’s reference-room result at 3 m; actual room levels depend on installation and acoustics. Heating ratings at other water temperatures must come from manufacturer selection data.